A thermodynamic evaluation on high pressure condenser of double effect absorption refrigeration system
[ X ]
Tarih
2016
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Pergamon-Elsevier Science Ltd
Erişim Hakkı
info:eu-repo/semantics/closedAccess
Özet
One of the parameters affecting the COP of the absorption system can be considered as the thermal balance between the high pressure condenser (HPC) and the low pressure generator (LPG) since heat rejected from the HPC is utilized as an energy source by the LPG. Condensation of the water vapor in the HPC depends on the heat removal via the LPG. This circumstance is significant for making an appropriate design and a controllable system with high performance in practical applications. For this reason, a thermodynamic analysis for the HPC of a double effect series flow water/lithium bromide absorption refrigeration system was emphasized in this study. A simulation was developed to investigate the energy transfer between the HPC and LPG. The results show that the proper designation of the HPC temperature improves the COP and ECOP due its significant impact, and its value necessarily has to be higher than the outlet temperature of the LPG based on the operating scheme. Furthermore, the COP and ECOP of the absorption system can be raised in the range of 9.72-35.09% in case of 2 degrees C-temperature increment in the HPC under the described conditions to be applied. (C) 2016 Elsevier Ltd. All rights reserved.
Açıklama
Anahtar Kelimeler
Double effect absorption, Water/lithium bromide, High pressure condenser, Low pressure generator, Performance evaluation, Irreversibility
Kaynak
Energy
WoS Q Değeri
Q1
Scopus Q Değeri
Q1
Cilt
113